Pulse
Inputs
|
2
|
Status
Indicators
|
Logic side
LED
|
Input
signal type
|
Sinking, sourcing or differential |
Input
Impedance
|
2.0K
ohms nominal
|
Input
frequency (on pulse inputs)
|
80/160
KHz maximum
|
Count
value
|
32 bit signed integer |
Min.
Input On Voltage (or differential)
|
4.00V
|
Frequency
data
|
16
bit signed integer(Configurable for 1 second or 200 mS count)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The
OptiLogic OL2258 High Speed Pulse Counter module
provides for direct pulse counting for a variety of high speed pulse interface
applications. Typical applications include motion control, metering and
velocity measurement. The OL2258 contains on board intelligence necessary
for processing and counting pulse information as well as automatically
triggering control outputs. The OL2258 can be configured to operate in one of three pulse counting modes. These modes are 1) Pulse & Direction, 2)Up/Down Count and 3) Quadrature . Pulse & Direction and Up/Down count will operate at up to 80KHz input pulse rates. Quadrature inputs count each quadrature state transitions at up to 160 KHz. Additionally, the OL2258 will return frequency information. |